Uninterruptible Power Supply |
| SENTRY HPS HT 10-80kVA |
|
Three Phase in Three Phase Out
>> Download Datasheet PDF
|
| Quality power supply |
Sentry HPS is an On-Line double conversion (VFI) UPS with filtered and stabilized sinusoidal output voltage. Sentry HPS is immune to the interferences on the electric power supply line as it has special input and output filters. |
| Maximum reliability and power availability |
The digital control of the appliance considerably improves reliability, since a reduction in electronic components lowers the likelihood of breakdowns. Digital control is provided by the microprocessor that, in the HPS series, controls all the internal parameters, thus increasing reliability and performance. In parallel connections, digital control ensures balance of the currents, which generally change over time due to phenomena such as vibrations and temperature, between the UPS units and the exchange of information with no need for manual tuning. Sentry HPS has been designed so that it can be connected in parallel even after the installation of the first unit. The power availability can be increased thanks to various configurations available such as the parallel configuration, the Dual Bus function and the Dynamic Dual Bus system. |
| High Efficiency |
If required, the unit can work in ECO mode to increase efficiency up to 98% and consequently reduce energy dissipation and costs. In this operating mode the mains is the priority source and the load is switched over to the Inverter only when the mains characteristics exceed the preset limits. |
| UPS for Industrial loads |
Sentry HPS with its strong overload capability, output galvanic isolation and low harmonic current distortion, is the ideal solution for industrial applications. Thanks to the high battery current, HPS Series is suitable to work with large battery banks as it can guarantee recharging in 10 hours as recommended by the battery manufacturer. |
Operating flexibility |
Sentry HPS is an uninterruptible power supply with On-Line double conversion technology that can also operate in Line Interactive mode (Economy mode for units over 100 kVA). All power ratings of the HPS series can also be used as Frequency Converters 50 to 60 Hz and vice versa. |
|
Mimic panel |
The mimic panel allows easy and intuitive operation of the UPS. It gives access to the most important parameters: status and alarms, control commands, input, output, battery measurements (power, current, voltage, frequency and temperature) and settings. The Sentry HPS diagnostics system includes up to 128 alarms or messages allowing precise and detailed identification of any event. |
| Maximum battery care |
Optimal battery management includes: - periodic battery test,
- protection against deep discharge,
- recharge temperature compensated.
|
| Motor Generator friendly |
Thanks to the range of different UPS versions and to the input filter solutions, Sentry HPS Series modules offer low harmonic distortion and high power factor at the input. This makes them ideal for use in conjunction with the Motor Generator at the input. On request, the HPS Series is provided with a "Motor Generator kit" that will inhibit the battery recharging and/or synchronization with bypass. |
| Maximum safety for personnel |
The back feed protection device prevents any voltage back feed in the upstream distribution board, thus ensuring the safety of the maintenance personnel. |
| Front access |
| Sentry HPS has frontal access for all power and electronic components, even in those configurations with internal batteries. This reduces the floor space required and consequently reduces the installation costs. |
| Advanced communication |
EPI's Watch & Save software displays the most important information such as the input and output voltage, the load applied, the remaining back-up time, etc., in the form of bar graphs. The software is able to provide information even in the event of a failure, in support of the fault diagnostics. The Watch & Save software can be used to program the automatic shutdown of all open systems in the event of a prolonged black out. Sentry HPS can also operate with a network agent for applications on LAN or WAN networks.
The UPS contains the following hardware interfaces:
- RS232 serial port,
- Dry contacts,
- EPO (Emergency Power Off) contact for UPS shutdown using the remote emergency button.
|
| Remote Service Support |
| TELEGUARD is a remote troubleshooting system that can signal any kind of unexpected event in real time. Any fault is immediately signalled, 24 hours a day, 365 days a year, to the service control centre, which can take immediate action either remotely or on site. Plus, a report is provided periodically, detailing all the most important events that have taken place during the monitored period. |
| Expandability |
| The units can be connected in parallel up to 8 units to increase power availability or redundancy. The single module or the system can be expanded any time to suit power requirements without influencing the initial investment. Thanks to the peculiarity of the "Hot System Expansion" feature, the additional unit can be connected in parallel while the other units are on-line and supplying regular power to the load. The new UPS is on-line and will be set up automatically. |
| Dual Bus System |
| The Dual Bus System powers the priority loads from two independent sources. This configuration increases the redundancy and availability level of a multi-module configuration. Each bus may consist of a single module or up to 8 modules in parallel, kept in synchro by the UGS (UPS Group Synchroniser). |
| Dynamic Dual Bus System |
| Two independent systems set in Dual Bus Configuration can be merged together at any time for system expansion or maintenance. This provides a lot of flexibility in your installation in case of maintenance or when it is necessary to change the redundancy level of both systems. |
| Applications |
| Servers, Local Area Network (LAN), Data centers, telecommunications, industrial equipment, electro-medical equipment. |
| Technical Data |
| Power VA |
Model |
Output
phases |
Dimensions
WXDXH (mm) |
Weight
(kg) |
| 10000 |
HT 10 |
3 + N |
555x720x1200 |
From 210 to 480 |
| 15000 |
HT 15 |
3 + N |
555x720x1200 |
From 220 to 470 |
| 20000 |
HM 20 |
3 + N |
555x720x1200 |
From 240 to 500 |
| 30000 |
HM 30 |
3 + N |
555x720x1200 |
From 282 to 610 |
| 40000 |
HM 40 |
3 + N |
555x720x1200 |
330 |
| 60000 |
HM 60 |
3 + N |
800x740x1400 (6p) 1070x740x1400 (12p) |
450 (6p) 600 (12p) |
| 80000 |
HM 80 |
3 + N |
800x740x1400 (6p) 1070x740x1400 (12p) |
555 (6p) 780 (12p) |
|
| SENTRY HPS HT 10-80 kVA |
| Model |
HT 10 |
HT 15 |
HT 20 |
HT 30 |
HT 40 |
HT 60 |
HT 80 |
| Input Voltage |
400 V three-phase + N |
| Voltage tolerance |
± 20% |
| Accepted frequency |
45÷60 Hz |
| Current distortion |
8% with input filter |
5% with input filter |
| Power factor |
0.9 with input filter |
0.92 with input filter |
| Soft start |
0 - 100% in 10'' |
| Rated voltage |
400 V three-phase + N |
| Voltage tolerance |
± 15% (selectable from ± 10% to ± 25% from front panel) |
| Rated frequency |
50 / 60 Hz |
| Frequency tolerance |
± 2% (selectable from ± 1% to ± 5% from front panel) |
| Bypass |
Static and manual for maintenance |
| Number of battery cell (Pb) |
192 |
| Nominal battery voltage |
430 V V |
| Type |
Maintenance-free sealed lead-acid |
| Maximum recharge current |
0,2xC10 |
35 A |
| Recharging voltage |
Variable according to the temperature (-0,5 V x °C) |
| Ripple current |
<1% |
| Rated power |
10000 VA |
15000 VA |
20000 VA |
30000 VA |
40000 VA |
60000 VA |
80000 VA |
| Active power at cos 0,8 |
8 kW |
12 kW |
16 kW |
24 kW |
32 kW |
48 kW |
64 kW |
| Phases number |
3 + N |
| Waveform |
Sinewave |
| Rated voltage |
380-400-415 V (selectable) three-phase + N |
| Frequency |
50 or 60 Hz |
| Frequency stability |
± 0,05% in battery operation, ± 2% in synchronism with mains (± 5% selectable) |
| Dynamic stability |
± 5% |
| Static stability |
± 1% |
| Crest factor (Ipeak/Irms) |
3 : 1 |
| Rated current |
14 A |
22 A |
29 A |
43 A |
58 A |
87 A |
115 A |
| Overload |
110% for 300', 125% for 10', 150% for 1' |
| AC/AC efficiency |
> 91% |
92% |
| Noise |
48-54 dBA at 1 m. |
53-60 dBA at 1 m. |
53-62 dBA at 1 m. |
| Operating temperature |
0 + 40°C |
| Relative humidity |
95 % non condensing |
| Remote controls |
EPO and bypass |
| Remote signals |
Volt free contacts (mains power failure, UPS on bypass, end of discharge pre-alarm, output 12Vdc 80mA) |
| Standards |
Safety EN 62040-1, EMC IEC 62040-2, and EN 50091-2, Directives 73/23, 93/68, 89/336 EEC, EN 62040-3 |
| Back-feed protection |
Standard |
| Protection degree |
IP20 |
| Colour |
Light grey RAL 7035 |
|
 |
| Product Image |
|
Product characteristics may be changed to meet specific customer demands
To find out more, please call one of our consultants on 01993 708855 or email sales@epi-uk.com |
|
|